Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter
Automatische name übersetzung:
Standard Test Method for Hitze und sichtbare Rauchfreisetzungsratenfür Materialien und Produkte unter Verwendung eines Sauerstoff Verbrauchskalorimeter
NORM herausgegeben am 10.1.2002
Bezeichnung normen: ASTM E1354-99
Anmerkung: UNGÜLTIG
Ausgabedatum normen: 10.1.2002
SKU: NS-41463
Zahl der Seiten: 18
Gewicht ca.: 54 g (0.12 Pfund)
Land: Amerikanische technische Norm
Kategorie: Technische Normen ASTM
Keywords:
cone calorimeter, heat-heat release rate, ignitability-radiant ignition, mass-mass loss rate, oxygen consumption method-heat release rate, smoke, ICS Number Code 17.200.10 (Heat. Calorimetry)
1. Scope | ||||||||||||||||||||||
1.1 This fire-test-response standard provides for measuring the response of materials exposed to controlled levels of radiant heating with or without an external ignitor. 1.2 This test method is used to determine the ignitability, heat release rates, mass loss rates, effective heat of combustion, and visible smoke development of materials and products. 1.3 The rate of heat release is determined by measurement of the oxygen consumption as determined by the oxygen concentration and the flow rate in the exhaust product stream. The effective heat of combustion is determined from a concomitant measurement of specimen mass loss rate, in combination with the heat release rate. Smoke development is measured by obscuration of light by the combustion product stream. 1.4 Specimens shall be exposed to heating fluxes in the range of 0 to 100 kW/m2. External ignition, when used, shall be by electric spark. The value of the heating flux and the use of external ignition are to be as specified in the relevant material or performance standard (see X1.2). The normal specimen testing orientation is horizontal, independent of whether the end-use application involves a horizontal or a vertical orientation. The apparatus also contains provisions for vertical orientation testing; this is used for exploratory or diagnostic studies only. 1.5 Ignitability is determined as a measurement of time from initial exposure to time of sustained flaming. 1.6 This test method has been developed for use for material and product evaluations, mathematical modeling, design purposes, or development and research. Examples of material specimens include portions of an end-use product or the various components used in the end-use product. 1.7 The values stated in SI units are to be regarded as the standard. 1.8 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions. 1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see Section 7. |
||||||||||||||||||||||
2. Referenced Documents | ||||||||||||||||||||||
|
Wollen Sie sich sicher sein, dass Sie nur die gültigen technischen Vorschriften verwenden?
Wir bieten Ihnen Lösungen, damit Sie immer nur die gültigen (aktuellen) legislativen Vorschriften verwenden könnten.
Brauchen Sie mehr Informationen? Sehen Sie sich diese Seite an.
Letzte Aktualisierung: 2024-05-17 (Zahl der Positionen: 2 902 148)
© Copyright 2024 NORMSERVIS s.r.o.